Treffer: Fault Location Based on Comprehensive Grey Correlation Degree Analysis for Flexible DC Distribution Network.
Weitere Informationen
Flexible DC distribution networks have a strong capacity for new energy consumption and have received extensive attention from scholars in recent years, but fault location for DC distribution lines is a difficult task. To solve this problem, we propose using a comprehensive grey correlation degree analysis to analyze the similarity of aerial mode traveling differential current waveforms at the first and last ends of a DC line, thus achieving fault location by obtaining the optimal time shift. Additionally, we built a six-terminal flexible DC distribution network model in Matlab/Simulink for simulation and validation, showing that the method can complete the rapid and accurate location of all types of faults on a DC line, and that it possesses an anti-transition resistance capability, making it suitable and highly reliable for cases of low sampling frequency. [ABSTRACT FROM AUTHOR]
Copyright of Energies (19961073) is the property of MDPI and its content may not be copied or emailed to multiple sites without the copyright holder's express written permission. Additionally, content may not be used with any artificial intelligence tools or machine learning technologies. However, users may print, download, or email articles for individual use. This abstract may be abridged. No warranty is given about the accuracy of the copy. Users should refer to the original published version of the material for the full abstract. (Copyright applies to all Abstracts.)